skip to main content

Rancang Bangun Alat Monitoring Breaker Motor 3 Fasa Berdasarkan Konfigurasi Breaker PLTU UBP Priok Dengan Pengukuran Keserempakan Serta Tegangan Secara Real-Time Berbasis Modul Optocoupler AC Serta Sensor ZMPT101B Dan Internet Of Things

*Melissa Rahmawati Yusuf  -  Universitas Diponegoro, Indonesia
Eko Ariyanto  -  Universitas Diponegoro, Indonesia

Citation Format:
Abstract

This monitoring system was designed to automatically detect breaker status based on 24V DC voltage, utilizing a 25V DC sensor. The system is capable of transmitting real-time data with an average response time of 9 seconds. The ZMPT101B voltage sensor used in the setup demonstrated low error rates, with 0.97% for phase R, 0.91% for phase S, and 0.58% for phase T. Additionally, an AC optocoupler module was employed to detect 220V AC, enabling accurate synchronization measurement. Results indicate that synchronization during the "on" condition is highly accurate, although a slight delay was observed during the "off" condition due to residual current in the signal amplification transistor (S8050) located within the module. Testing at the Priok UBP Combined-Cycle Power Plant confirmed that the system meets the company's configuration standards, with an obtained the best value of 2 ms with average time of  3.2 ms, suggesting that the breakers operate within optimal parameters. Overall, the system performs effectively and aligns with the company’s operational requirements.

Keywords: ZMPT101B Sensor, AC Optocoupler Module, Breaker Synchronization

Article Metrics:

  1. D. A. Jujun Tugistan, F. Dheny Cipta, and H. Mohammad Rizal, “AJIKER (ALAT UJI BREAKER): TOOLS UNTUK MEMPERCEPAT RECOVERY GANGGUAN DALAM TROUBLESHOOTING DAN PENGUJIAN BREAKER MCC 400V MODUL GT/HRSG/ST.” 2022
  2. M. Basten Raja Sipahutar, “Rancang Bangun Alat Tes Individual Circuit Breaker (CB) 3 Phasa di PLTU UNIT PELAKSANA PEMBANGKITAN (UPK) BELAWAN.” Medan, 2021
  3. ALL-TESTPPRO, “DAMPAK KETIDAKSEIMBANGAN TEGANGAN.” [Online]. Available: https://alltestpro.com/id/dampak-ketidakseimbangan-tegangan/
  4. Basic Electronics Tutorials, “Rectification of a Three Phase Supply using Diodes.” Accessed: Jul. 15, 2024. [Online]. Available: https://www.electronics-tutorials.ws/power/three-phase-rectification.html
  5. A. G. Firdaus and R. Hidayat, “Analisis Pengujian Kelayakan PMT 150 kV Bay Mandirancan I Berdasarkan Parameter Breaker Analyzer di Gardu Induk Sunyaragi,” Elektron J. Ilm., vol. 13, no. 17–24, 2021, doi: https://doi.org/10.30630/eji.0.0.217
  6. S. Budi, Wisnu, and Dkk, “KARAKTERISASI SENSORARUS DAN TEGANGAN UNTUK APLIKASI MAXIMUM POWER POINT TRACKER PADA SISTEM PENYIMPANAN ENERGI LISTRIK PANEL SURYA,” Pros. Semin. Nas. Fis., vol. IX, 2020
  7. A. Putra, Deni, and R. Mukhaiyar, “Monitoring Daya Listrik Secara Real Time,” J. Vocat. Tek. Elektron. dan Inform., vol. 8, no. 2, 2020
  8. Muliadi and dkk, “PENGEMBANGAN TEMPAT SAMPAH PINTAR MENGGUNAKAN ESP32,” J. Media Elektr., vol. 17, no. 2, 2020
  9. “ESP32 DEVKITC V4.” [Online]. Available: https://www.espressif.com
  10. W. Wasana, Fredi, and S. Delliana, “PEMANFAATAN GOOGLE FORM DAN GOOGLE SPREEDSHEETDI LEARNING RESOURCE CENTER (LRC) INSTITUT TEKNOLOGI DAN BISNIS KALBIS,” J. Perpust. dan Inf. Undip Ed. Mei 2021, 2021

Last update:

No citation recorded.

Last update: 2026-11-05 12:43:49