skip to main content

UNJUK KERJA TRANSFORMATOR DAYA PADA GARDU INDUK SISTEM KELISTRIKAN PULAU BANGKA

Bambang Irawan  -  Jurusan Teknik Elektro, Fakultas Teknik, Universitas Bangka Belitung, Indonesia
*Wahri Sunanda scopus  -  Jurusan Teknik Elektro, Fakultas Teknik, Universitas Bangka Belitung, Indonesia
Dikirim: 27 Peb 2020; Diterbitkan: 30 Jun 2020.
Akses Terbuka Copyright (c) 2020 Transmisi under http://creativecommons.org/licenses/by-sa/4.0.

Citation Format:
Sari
Efisiensi transformator dapat didefinisikan sebagai perbandingan antara daya listrik keluaran dengan daya listrik yang masuk pada transformator.  Oleh karenanya akan dianalisis pengaruh perubahan beban terhadap efisiensi dan rugi-rugi  transformator daya di gardu induk Air Anyir, gardu induk Pangkalpinang dan gardu induk Sungailiat. Hasil analisis yang didapatkan pada transformator daya gardu induk Air Anyir pembebanan tertinggi 13.36 MW dengan efisiensi 99.62 % dan rugi total 49.46 kW serta pembebanan terendah sebesar 2.37 MW dengan efisiensi 96.65 % dan rugi total 38.83 kW. Pada tranformator daya gardu induk Pangkalpinang pembebanan tertinggi 17,38 MW dengan efisiensi 99.69 % dan rugi total 61.64 kW serta  pembebanan terendah 11.93 MW dengan efisiensi 99.65 % dan rugi total 41.22 kW. Pada  transformator daya gardu induk Sungailiat pembebanan tertinggi 12.98 MW dan efisiensi 99.65 %, dan rugi total 45.61 kW sedangkan pembebanan terendah 2.06 MW dengan efisiensi 97.46% dan rugi total 23.88 kW
Fulltext View|Download
Kata Kunci: efisiensi transformator; pembebanan; rugi total; gardu induk

Article Metrics:

  1. . PLN Wilayah Bangka Belitung. Kondisi Kelistrikan Februari. 2019
  2. . BPS Provinsi Kepulauan Bangka Belitung. Provinsi Kepulauan Bangka Belitung Dalam Angka. 2019
  3. . W. Sunanda. Studi Unjuk Kerja Pembangkit Listrik Tenaga Uap (PLTU) Air Anyir Bangka. Setrum: Sistem Kendali-Tenaga-elektronika-telekomunikasi-komputer, 2019, 8(2),hal: 248-252
  4. . M. R. Khan, A. Kumar, A. Patra. Process of Energy Audit of Commercial Building and Substation. International Journal of Engineering Research and Application, 2013, Vol. 3 No. 4 . hal : 861-869
  5. . E. Cazacu, M. Stanculescu, I.V. Nemoianu. Power Substation Energy Efficiency Analysis-A Case Study. Journal of Electrical and Electronics Engineering, 2011, 4(1)
  6. . K.D. McBee, J. Chong, P. Rudraraju. Demand Side Management Effects on Substation Transformer Capacity Limits. Applied Sciences, 2019, 9(16), 3266
  7. . W. Yuekang, C. Shuheng, J. Shi, and S. Xueting, A research based on testing method for the whole substation cascaded in digital substation, E3S Web of Conferences, 2018, vol. 64, p. 04002
  8. . Bowen. Substation commissioning and turnover planning, IEEE Industry Applications Magazine, 2000, vol. 6, no. 2, pp. 8–22
  9. . R. Syahputra and L. F. Arrozak, Power Transformer Loading Analysis in Order to Improve the Reliability of a Substation, Journal of Electrical Technology UMY, 2017, vol. 1, no. 4
  10. . S. Guseva, O. Borscevskis, N. Skobeleva, L. Kozireva. Load Determination and Selection of Transformer Substations' Optimal Power for Tasks of Urban Networks' Development, Electrical, Control and Communication Engineering, 2010 vol. 26, no. 1, pp. 31-36
  11. . T.A. Darsono, N. Patawaran, C. Chotimah . Voltage Data Reporting Application On The Electrical Substation At PT. Haleyora Powerindo Merauke. In IOP Conference Series: Earth and Environmental Science. 2019, Vol. 343, No. 1. IOP Publishing
  12. . F. Enemuoh, T.L Alumona, C.H. Aliche. Investigation Of Energy Loss In A Transmission Substation Using Onitsha 330/132kv As A Case Study. International Journal of Technical Research and Applications. 2016, Volume 4, Issue 4. pp. 36-40
  13. . PLN Area Bangka. Data Efisiensi Gardu Induk Air Anyir, Gardu Induk Pangkalpinang, Gardu Induk Sungailiat. 2018
  14. . SPLN No 61 Tahun 1997. Spesifikasi Transformator Tenaga Tegangan Tinggi. Jakarta : SPLN; 1997
  15. R. Syahputra and L. F. Arrozak, Power Transformer Loading Analysis in Order to Improve the Reliability of a Substation, Journal of Electrical Technology UMY, 2017, vol. 1, no. 4

Last update:

No citation recorded.

Last update: 2024-10-07 21:19:29

No citation recorded.