@article{Transmisi307, author = {Abdul Syakur dan Agung Warsito}, title = {KINERJA ARRESTER AKIBAT INDUKSI SAMBARAN PETIR}, journal = {Transmisi: Jurnal Ilmiah Teknik Elektro}, volume = {11}, number = {1}, year = {2010}, keywords = {}, abstract = { Electricity demand continues to increase so that the required power in a large number of high quality and reliability. Problems in electric power system that occur in transmission and distribution lines that is often of lightning stroke. This is because Indonesia is in the region the equator with a tropical climate and high humidity, so that Indonesia has a number of lightning strikes. In this paper the lightning stroke and lightning arrester performance on distribution lines 20 kV were simulated using EMTP (Electromagnetic Transient Program) for lightning stroke observation. As case study, Mojosongo 1 main feeder 20 kV three phase lines were used. From simulation of lightning stroke 20 kA in By1-61-61E-84-9I on S phase at 0,1 ms, will experience of increase of voltage on S phase was 1,3054 MV and for R phase and T phase will experience of increase of induced voltage were 0,79539 MV and 0,80484 MV. Then we will see performance of MOV Arrester (Metal Oxide Varistor) in overcoming lightning stroke trouble, where arrester can decrease voltage up to 15,198 kV on S phase, while at R phase and T phase arrester can decrease voltage up to 11,375 kV and 13,616 kV. Keywords: Distribution lines 20 kV, lightning arrester, lightning stroke. }, issn = {2407-6422}, pages = {9--15} doi = {10.12777/transmisi.11.1.9-15}, url = {https://ejournal.undip.ac.id/index.php/transmisi/article/view/307} }
Refworks Citation Data :
Electricity demand continues to increase so that the required power in a large number of high quality and reliability. Problems in electric power system that occur in transmission and distribution lines that is often of lightning stroke. This is because Indonesia is in the region the equator with a tropical climate and high humidity, so that Indonesia has a number of lightning strikes.
In this paper the lightning stroke and lightning arrester performance on distribution lines 20 kV were simulated using EMTP (Electromagnetic Transient Program) for lightning stroke observation.
As case study, Mojosongo 1 main feeder 20 kV three phase lines were used. From simulation of lightning stroke 20 kA in By1-61-61E-84-9I on S phase at 0,1 ms, will experience of increase of voltage on S phase was 1,3054 MV and for R phase and T phase will experience of increase of induced voltage were 0,79539 MV and 0,80484 MV. Then we will see performance of MOV Arrester (Metal Oxide Varistor) in overcoming lightning stroke trouble, where arrester can decrease voltage up to 15,198 kV on S phase, while at R phase and T phase arrester can decrease voltage up to 11,375 kV and 13,616 kV.
Article Metrics:
Last update:
Last update: 2024-11-15 13:16:29
Transmisi: Jurnal Ilmiah Teknik Elektro dan Departemen Teknik Elektro, Universitas Diponegoro dan Editor berusaha keras untuk memastikan bahwa tidak ada data, pendapat, atau pernyataan yang salah atau menyesatkan dipublikasikan di jurnal. Dengan cara apa pun, isi artikel dan iklan yang diterbitkan dalam Transmisi: Jurnal Ilmiah Teknik Elektro adalah tanggung jawab tunggal dan eksklusif masing-masing penulis dan pengiklan.
Formulir Transfer Hak Cipta dapat diunduh di sini: [Formulir Transfer Hak Cipta Transmisi]. Formulir hak cipta harus ditandatangani dan dikirim ke Editor dalam bentuk surat asli, dokumen pindaian atau faks:
Dr. Munawar Riyadi (Ketua Editor)Departemen Teknik Elektro, Universitas Diponegoro, IndonesiaJl. Prof. Sudharto, Tembalang, Semarang 50275 IndonesiaTelepon/Facs: 62-24-7460057Email: transmisi@elektro.undip.ac.id