STUDY ON SURGE ARRESTER PERFORMANCE DUE TO LIGHTNING STROKE IN 20 KV DISTRIBUTION LINES

*Agung Warsito  -  , Indonesia
Abdul Syakur  -  , Indonesia
Liliyana N.S.  -  , Indonesia

Citation Format:
Abstract
Electric energy has been transmiting from power station to end user with transmission and distribution lines.Lightning strokes are problems that occure in transmission and distribution lines and make them fault when theelectric energy were transmited. Surge Diverter or Lightning Arrester has been installing to reduce these faults.In this paper the simulation of lightning stroke and lightning arrester performance on distribution lines 20 kVwere done using EMTP (Electromagnetic Transient Program). Some parameters such us impuls voltage andincreasing voltage on distribution line was inverstigated. As case study in this simulation, Mojosongo 1 mainfeeder 20 kV three phase lines were used.The simulation results show that the lightning stroke 20 kA in By1-61-61E-84-9I on S phase at 0,1 ms, makevoltage on S phase was increased about 1,3054 MV. For R phase and T phase will increase of induced voltagewere 0.79539 MV and 0.80484 MV. We also show the performance of MOV Arrester (Metal Oxide Varistor) inovercoming lightning stroke trouble, where arrester can decrease voltage up to 15.198 kV on S phase, while atR phase and T phase arrester can decrease voltage up to 11.375 kV and 13.616 kV.
Fulltext View|Download
Keywords: Distribution lines 20 kV, surge arrester, lightning stroke.